Electrical Wire Sizing & Voltage Drop Calculator
Size copper and aluminum conductors (AWG / kcmil) to limit circuit voltage drop according to National Electrical Code (NEC) standards.
Electrical Analysis Summary
Calculated Voltage Drop
0.00 V
Percentage Drop (%)
0.00 %
Voltage at Load Terminal
0.0 V
Power Loss in Conductor
0.0 W
Recommended Min. Gauge for Selected Drop Limit
12 AWG
Compliance Status
OK
Electrical Engineering Formulas & NEC Guidelines
Excessive voltage drop across long conductor runs causes equipment inefficiency, motor overheating, flickering lights, and wasted energy dissipated as heat.
1. Voltage Drop Equations
For Single-Phase AC and DC circuits (2-wire systems):
ΔV = (2 * K * I * L) / CM
For Three-Phase AC circuits (balanced line-to-line):
ΔV = (1.732 * K * I * L) / CM
K= Conductor resistivity constant (approx. 12.9 Ω·cmil/ft for Copper; 21.2 Ω·cmil/ft for Aluminum at 75°C)I= Load current in AmperesL= One-way length of the run in feetCM= Conductor cross-sectional area in Circular Mils
2. National Electrical Code (NEC) Standards (Article 210.19 & 215.2)
The NEC recommends that branch circuit conductors be sized so that the maximum voltage drop does not exceed 3% at the farthest outlet. The maximum combined drop for both feeder conductors and branch circuits combined should not exceed 5% for overall system operating efficiency.
3. Standard AWG Conductor Cross-Section Reference
| AWG / kcmil Size | Circular Mils (cmil) | Typical 75°C Copper Ampacity (THHN) |
|---|---|---|
| 14 AWG | 4,110 | 20 A (Max 15A Breaker) |
| 12 AWG | 6,530 | 25 A (Max 20A Breaker) |
| 10 AWG | 10,380 | 35 A (Max 30A Breaker) |
| 8 AWG | 16,510 | 50 A |
| 6 AWG | 26,240 | 65 A |
| 4 AWG | 41,740 | 85 A |
| 2 AWG | 66,360 | 115 A |
| 1/0 AWG | 105,600 | 150 A |
| 4/0 AWG | 211,600 | 230 A |